Fujitsu SPARC T5120 Instrukcja Użytkownika Strona 154

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 153
128 SPARC Enterprise T5120 and T5220 Servers Service Manual July 2009
FIGURE: Installing a Fan Module
2. Apply firm pressure to fully seat the fan module.
3. Verify that the Fan Fault LED on the replaced fan module is off.
4. Close the top cover door.
5. Verify that the system Fan Fault LED, Service Required LEDs, and the
individual fan module Fault LED are off.
6. Run the ILOM show faulty command to verify that the fan fault has been
cleared.
See “Detecting Faults With ILOM” on page 22 for more information on using the
show faulty command.
Related Information
“Extend the Server to the Maintenance Position” on page 63
“Faults Displayed by show faulty on page 29
Przeglądanie stron 153
1 2 ... 149 150 151 152 153 154 155 156 157 158 159 ... 239 240

Komentarze do niniejszej Instrukcji

Brak uwag